13 Parameter reference
13.1 Parameters of the communication module
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13852
C13853
C13860
Parameter | Name:
C13852 | All words to standard device
Data type: UNSIGNED_16
Index: 10723
d
= 29E3
h
Display of process data words 1 ... 16 which are transferred from the communication module to the standard device.
In subcodes 1 ... 16, all process data words from the communication module are displayed.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13852/1
...
C13852/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13853 | All words from standard device
Data type: UNSIGNED_16
Index: 10722
d
= 29E2
h
Display of process data words 1 ... 16 which are transferred from the standard device to the communication module.
In subcodes 1 ... 16, all process data words from the standard device are displayed.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13853/1
...
C13853/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13860 | Settings
Data type: UNSIGNED_8
Index: 10715
d
= 29DB
h
Display of the current configuration data.
Display area (min. value | unit | max. value)
0 255
Subcodes Info
C13860/1 Reserved
C13860/2 Number of process data words (1 ... 16 words)
C13860/3 DRIVECOM parameter data channel
0: Not active
•1: Active
C13860/4 Reserved
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT