3.6.4.4 - Control via terminal block - 4 preset frequencies
M
1
+24V (positive logic)
0V (negative logic)
Unlock
Run forward/Stop
Run reverse/Stop
Reference selection
Reference selection
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Fault relay
Term. 12 Term. 13 Reference Assoc. parameter
0 0 Preset frequency no. 1 (FP1) 11
1 0 Preset frequency no. 2 (FP2) 12
0 1 Preset frequency no. 3 (FP3) 13
1 1 Preset frequency no. 4 (FP4) 14
Analogue output (motor frequency)
Logic output (zero frequency)
PL1
PL2
The original configuration of the drive assumes positive logic
operation.
Using a drive with a control system which has a different control logic
may cause unwanted starting of the motor.
See section 4.4 for configuring the drive for negative logic, and connect
the common to 0V.