Troubleshooting
54 SOLID-4 Leuze electronic
DEUTSCH ENGLISH FRANÇAIS ITALIANO ESPAÑOL NEDERLANDS
10.3 AutoReset
After an error or a fault has been detected and indicated, with the exception of the locking
error/fault, a restart follows automatically
in the transmitter after about 10 seconds and
in the receiver after about 10 seconds.
for the device in question. If the error or fa
ult is then no longer present, the machine/
application can be started again. The temporary error signal, however, is then lost.
*With locking errors (F6, F8, F10, F25, F26, F32, F33, F34, F35, F37 [conditional: F30]) the
receiver i
s not automatically reset after 10 seconds. The receiver goes instead to the error
locking status, from which it can only come out of by switching the supply voltage off and
back on again.