EasyManua.ls Logo

LG MULTI F

LG MULTI F
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Design pressure is 551 psig.
All dimensions in inches. Tolerance ±1/4 inch.
Images are not to scale.
REFRIGERANT PIPING DESIGN
LG Engineered Multi F MAX Y-Branch Kit
The LG supplied Y-Branch Kit PMBL5620 MUST be used when two
branch distribution units are connected on one Multi F MAX system.
Field-supplied fittings are not permitted. Each Y-Branch kit comes
with two (2) Y-branches (one for the liquid line and one for the vapor
line) and insulation covers.
Y-branches may be installed in horizontal or vertical configurations.
When installed vertically, position the Y-branch so the straight-
through leg is ±3° of plumb. When installed horizontally, position the
Y-branch so the take-off leg is level and shares the same horizontal
plane as the straight-through leg ±10° rotation.
Y-branches must be properly installed following instructions in the
applicable LG manual. Y-branches should always be installed with
the single port facing the outdoor unit and the two-port end facing
the branch distribution units. Do not install Y-branches backwards
as refrigerant flow cannot make U-turns. The Y-branch kit must be
located at least three (3) feet from the outdoor unit. Provide
a minimum of 20 inches between a Y-branch and the branch
distribution unit.
It is recommended that when a Y-branch is located in a pipe chase
or other concealed space, access doors should be provided for
inspection access.
The equivalent pipe length of each Y-branch (1.6′) must be added to
the main pipe segment entered into LATS piping design software.
Figure 257:Y-Branch Connections.
Figure 258:Y-Branch Dimensions Diagram.
Figure 259:Horizontal Conguration End View.
Multi F MAX Y-Branch Kit PMBL5620
Table 110:Y-Branch Connection Diameters.
Model
Y-Branch
Type
Port Identier (inch) Dimensions
1 2 3 X Y
PMBL5620
Liquid 3/8 3/8 3/8 13.80 3.24
Vapor 3/4 3/4 3/4 12.48 3.02
To Branch Distribution Unit Ø3/4
Ø3/4
To Outdoor Unit
Ø3/4
Ø3/8
Ø3/8
To Outdoor Unit
To Branch Distribution Unit Ø3/8
Y-Branch Kit Insulation
Each Y-branch kit comes with clam-shell type peel-and-stick insula-
tion jackets molded to fit the Y-branch fittings—one for the liquid
line, one for the vapor line.
Check the fit of the Y-branch clam-shell insulation jacket after the
Y-branch is installed.
Mark the pipe where the insulation jacket ends.
Remove the jacket.
Install field-provided insulation on the pipes first.
Peel the adhesive glue protector slip and install the clam-shell
jacket over the fitting
Figure 260:Y-branch Installation Alignment Specication.
Viewed from A in direction of arrow
Horizontal
plane
Within 10°
A
Vertical Up
Configuration
Within ± 3°Within ± 3°
Vertical Down
Configuration
Liquid and Gas
Pipe Joints
Y-Branch Kit Insulation
Insulation for
Field-Installed Piping
Field-Supplied Insulation Tape
A
B
X
Y
1
2
3
A = To Outdoor Unit
B = To Branch
Distribution Unit
Figure 261:Y-branch Insulation Detail.
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DESIGN & PRACTICES | 195
Refrigerant Piping Design and Best Practices
MULTI
F
MAX
MULTI
F

Table of Contents

Other manuals for LG MULTI F

Related product manuals