Installation of water tank
Installation of floor heating
Strainer
- Use the 28 mesh strainer.
(Exclude scale diameter of 0.4 mm or less and other net)
- Check the strainer direction and assemble on the inlet hole (Refer to picture)
- Wrap the Teflon tape on the screw thread of the water pipe for more than 15 times for
assembly.
- Install the service port facing downward. (Within left/right 45 degrees)
- Check if there is any leakage on the connecting part.
- Clean the strainer periodically. (Once a year or more frequent)
shut-off valve (2)
Pump (1)
Flexible joint (3)
Pressure gauge (4)
Water supply valve (6)
water tank (9)
(Indirect heating type)
Expansion tank (5)
Heat
exchange
coil (8)
water tank
temperature sensor (7)
shut-off valve (2)
Pump (1)
Flexible joint (3)
Pressure gauge (4)
Water supply valve (6)
Floor heating coil
(Radiator, FCU can be used)
Expansion tank (5)
Water In
Strainer
Front Side
45°

Table of Contents

Other manuals for LG THERMA V Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG THERMA V Series and is the answer not in the manual?

LG THERMA V Series Specifications

General IconGeneral
BrandLG
ModelTHERMA V Series
CategoryHeat Pump
LanguageEnglish

Related product manuals