Maintenance
39 Liebert
®
GXT4
10. Reattach the front battery door with the six screws.
11. Reattach the front plastic bezel cover to the UPS.
6.2 Battery Charging
The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their
design life. The Liebert GXT4 charges the batteries continuously when it is connected to the mains
input power.
If the Liebert GXT4 will be stored for a long time, Emerson recommends connecting the UPS to input
power for at least 24 hours every three to four months to ensure full recharge of the batteries.
6.3 Precautions
Although the Liebert GXT4 has been designed and manufactured to ensure personal safety, improper
use can result in electrical shock or fire. To ensure safety, observe the following precautions:
Turn Off and unplug the Liebert GXT4 before cleaning it.
Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
Never block or insert any objects into the ventilation holes or other openings of the UPS.
Do not place the Liebert GXT4 power cord where it might be damaged.
6.4 Checking UPS Status
Emerson
®
recommends checking the UPS operation status every six months.
Check whether the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?
Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal
Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or
Emerson Channel Support.
Check whether the battery is discharging. When the mains input is normal, the battery should
not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson
representative or Emerson Channel Support.
NOTE
The internal battery pack is hot-swappable. However, caution should be exercised because
during this procedure the load is unprotected from disturbances and power outages.
Do not replace the battery while the UPS is in Battery Mode. This will result in a loss of output
power and will drop the connected load.

Table of Contents

Other manuals for Liebert GXT4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert GXT4 and is the answer not in the manual?

Liebert GXT4 Specifications

General IconGeneral
Form FactorTower/Rack Mount
Power Factor0.9
Battery TypeSealed Lead-Acid (SLA)
Backup TimeVaries by model and load
Waveform TypeSinewave
Communication PortsUSB, RS-232
TopologyOn-line Double Conversion
Output Frequency50/60 Hz +/- 0.1 Hz
Typical Recharge Time3 hours to 90%
Operating Temperature0°C to 40°C (32°F to 104°F)
Storage Temperature-15°C to 45°C (5°F to 113°F)
Humidity0-95% non-condensing
DimensionsVaries by model
WeightVaries by model
CertificationsUL, cUL, CE, RoHS
Output Voltage208/220/230/240VAC

Related product manuals