EasyManua.ls Logo

Liebert GXT4 - Page 51

Liebert GXT4
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
45 Liebert
®
GXT4
Table 15 Battery cabinet specifications
Parameter
Model Number
GXT4-48VBATT
GXT4-48VBATTE
GXT4-72VBATT
GXT4-72VBATTE
Used w/UPS Model
GXT4-700RT230/230E, GXT4-1000RT230/230E,
GXT4-1500RT230/230E, GXT4-2000RT230/230E GXT4-3000RT230/230E
Dimensions, D x W x H, mm (in)
Unit
497 × 430 × 85
(19.7 x 16.9 x 3.3)
602 × 430 × 85
(23.6 x 16.9 x 3.3)
Shipping
617 x 570 x 262
(24.3x 22.4 x 10.3)
717 x 570 x 262
(28.2 x 22.4 x 10.3)
Weight, kg (lb)
Unit 32 (70.5) 42 (92.6)
Shipping
39 (86)
“E” model 35 (77.2)
50 (110)
“E” model 46 (101.4)
Battery parameters
Type Valve-regulated, nonspillable, lead acid
Qty × V× Rating 2 × 4 × 12V × 9.0Ah 2 × 6 × 12V × 9.0Ah
Battery Mfr/Part# Panasonic/UP-RW1245 CSB/HR 1234W F2; CSB/UPS 12460 F2
Backup Time See Table 17 - Battery run times
Environmental
Operating Temperature 0ºC to 40ºC (32ºF to 104ºF)
Storage Temperature -15ºC to +40ºC (19ºF to 104ºF)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 3000m (10,000 ft.) at 40ºC (104ºF) without derating
Storage Elevation 15000m (50,000 ft.) maximum
Agency
Safety IEC/EN/AS 62040-1:2008, GS mark
RFI/EMI FCC Part 15, Class A=CISPR22 Class A
Surge Immunity IEC 62040-2 2nd Ed.: 2006
Transportation ISTA Procedure 1A
Table 16 Operating temperature parameters
Ambient Temperature, °C (°F) 25-30 (77-86) 30-35 (86-95) 35-40 (95-104)
Maximum Output Power Factor Derating
@ Maximum Load
100%-93% 93%-86% 86%-79%