Specifications
47 Liebert
®
GXT4
Internal Battery
+ 4 External
Battery Cabinets
10% 480 480 480 466 480
20% 480 460 444 421 423
30% 458 436 340 306 307
40% 442 340 309 192 192
50% 425 315 205 157 157
60% 336 218 165 142 143
70% 319 195 153 127 128
80% 301 165 141 107 109
90% 213 156 130 95 97
100% 197 147 112 80 81
Internal Battery
+ 5 External
Battery Cabinets
10% 480 480 480 480 480
20% 480 467 457 438 440
30% 465 447 431 331 332
40% 452 428 333 224 225
50% 438 341 307 189 189
60% 425 320 208 158 159
70% 344 227 167 146 147
80% 329 208 158 133 135
90% 315 189 148 120 122
100% 301 164 139 104 106
Internal Battery
+ 6 External
Battery Cabinets
10% 480 480 480 480 480
20% 480 480 466 450 452
30% 480 458 444 420 421
40% 462 442 422 319 319
50% 451 426 328 217 217
60% 440 341 305 186 187
70% 428 323 209 159 160
80% 368 306 184 148 150
90% 336 217 161 137 139
100% 325 201 153 126 128
* The times above are approximate. They are based on new, fully charged standard batteries at a temperature of
25°C (77°F) with 100% resistive UPS loading. The listed run times can vary by ±5% because of manufacturing variances of the
batteries.
Table 17 Battery run times (continued)
Number of
Batteries/Cabinets
Load Percent
of Capacity
Run Time, Minutes *
700VA 1000VA 1500VA 2000VA 3000VA

Table of Contents

Other manuals for Liebert GXT4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert GXT4 and is the answer not in the manual?

Liebert GXT4 Specifications

General IconGeneral
Form FactorTower/Rack Mount
Power Factor0.9
Battery TypeSealed Lead-Acid (SLA)
Backup TimeVaries by model and load
Waveform TypeSinewave
Communication PortsUSB, RS-232
TopologyOn-line Double Conversion
Output Frequency50/60 Hz +/- 0.1 Hz
Typical Recharge Time3 hours to 90%
Operating Temperature0°C to 40°C (32°F to 104°F)
Storage Temperature-15°C to 45°C (5°F to 113°F)
Humidity0-95% non-condensing
DimensionsVaries by model
WeightVaries by model
CertificationsUL, cUL, CE, RoHS
Output Voltage208/220/230/240VAC