ZERO PARAMETERS
RESETTABLE WEIGHT SETTING FOR SMALL WEIGHT CHANGES
 (from 0 to max full scale; default: 300; considered decimals: 300 30.0 3.00 0.300): this
parameter indicates the maximum weight value resettable by external contact, keypad or serial
protocol.
AUTOMATIC ZERO SETTING AT POWER-ON
 (from 0 to max 20% of full scale; default: 0): If at switch-on the weight value is lower than
the value set in this parameter and does not exceed the  value, the weight is reset. To
disable this function, set 0.
ZERO TRACKING
 (from 1 to 5, default: ): When the weight value is stable and, after a second, it
deviates from zero by a figure in divisions smaller or equal to the figure in divisions set in this
parameter, the weight is set to zero. To disable this function, set .
Example: if the parameter  is set to 5 and  is set to 2, the weight will be
automatically set to zero for variations smaller than or equal to 10 ( x ).


+
