3 Troubleshooting (continued)
Service Manual
51
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Outlet Temp
High
Outlet water temperature has exceeded the
maximum outlet water temperature.
• Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the boiler is piped properly into the heating
system. Refer to Section 5 - Hydronic Piping of the
Crest Installation and Operation Manual
for the proper piping methods for the Crest boiler.
Check for 120 vac to the boiler pump motor on a call
for heat. If voltage is not present, check wiring back
to the main control board. Replace the main control
board if necessary.
If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
Verify that the boiler pump is set to the proper speed
or that the boiler pump is the proper size. Reference
Section 5 - Hydronic Piping of the Crest Boiler
Installation and Operation Manual for boiler pump
specifications.
Inspect the outlet sensors and associated wiring.
Measure the resistance of the sensors and compare to
the tables in of this manual.
Parameter
Programming
Complete
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART TOUCH display
to reset.)
After downloading parameters from a laptop,
the main control board must be reset.
Press the RESET button on the SMART
TOUCH display panel.
Sensor Open
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
Either the inlet water or outlet water
temperature sensor has been disconnected.
Check the sensors and their associated wiring.
Repair or replace the sensor or wiring if damaged.
• Measure the resistance of the sensors and compare
the resistance to the tables in this manual.
Replace the sensor if necessary.
Sensor Shorted
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
Either the inlet water or outlet water
temperature sensor has been shorted.
Check the sensors and their associated wiring.
Repair or replace the sensor or wiring if damaged.
• Measure the resistance of the sensors and compare
the resistance to the tables in this manual.
Replace the sensor if necessary.
Flue Sensor
Open
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The flue sensor has been disconnected or
removed from the flue.
• Check the sensor and its associated wiring. Repair
or replace the sensor or wiring if damaged.
• Measure the resistance of the sensors and compare
the resistance to the tables in this manual.
Replace the sensor in flue.
Replace the sensor if necessary.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lochinvar Crest w/RealTime O2 Trim 100 Series and is the answer not in the manual?

Lochinvar Crest w/RealTime O2 Trim 100 Series Specifications

General IconGeneral
BrandLochinvar
ModelCrest w/RealTime O2 Trim 100 Series
CategoryBoiler
LanguageEnglish

Related product manuals