3 Troubleshooting
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Flue Sensor
Shorted
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The flue sensor has been shorted.
Check the sensor and its associated wiring. Repair
or replace the sensor or wiring if damaged.
Measure the resistance of the sensors and compare
the resistance to the tables in this manual.
Replace the sensor if necessary.
Too Many
Resets - Try Later
Too many manual resets have occurred
during a 15 minute period.
Wait 15 minutes and try again.
Turn power off to unit, wait 30 seconds and then turn
power back on.
Internal Fault
The main control board has detected an
internal fault.
Replace the main control board.
Flue Temp
Shutdown
The stack temperature has exceeded the
set parameters for the boiler.
Inspect the heat exchanger. Reference this manual
for the procedure on how to clean the flue side of the
heat exchanger.
Inspect the flue sensor and associated wiring.
Measure the resistance of the flue sensor and
compare to Table 3E of this manual. Replace the
sensor if necessary.
Verify that the vent/air intake pipes are properly
installed and that there are no obstructions.
Replace the main control board.
Delta T
Shutdown
The temperature rise across the heat
exchanger has exceeded the set parameters
for the boiler.
Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the boiler is piped properly into the heating
system. Refer to Section 5 - Hydronic Piping of the
Crest Installation and Operation Manual
for the proper piping methods for the Crest boiler.
Check for voltage to the boiler pump motor on a call
for heat. If voltage is not present, check the wiring
back to the pump relay. Replace the pump relay if
necessary.
If 120 VAC is present on a call for heat and the boiler
pump is not operating, replace the pump.
Verify that the boiler pump is set to the proper speed
or that the pump is the proper size. Reference
Section 5 - Hydronic Piping of the Crest
Installation and Operation Manual for boiler
pump specifications.
Service Manual
52

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lochinvar Crest w/RealTime O2 Trim 100 Series and is the answer not in the manual?

Lochinvar Crest w/RealTime O2 Trim 100 Series Specifications

General IconGeneral
BrandLochinvar
ModelCrest w/RealTime O2 Trim 100 Series
CategoryBoiler
LanguageEnglish

Related product manuals