5.4.3. Programmable transducer parameters
The table below shows programmable parameters and the
possiblerangesofvalues.
Table1
Settings
Input
Para-
meter
symbol
Description Range of changes
Input
Selection of
theinputtype
– measured
valuetype
Displayed symbol
Description
Voltage -10..10V
Voltage-10V…10V
Current -24..24V
Voltage-24V…24V
Current -20..20mA
Current-20mA…20mA
Resist. 400Ω Resistance 0 … 400Ω
Resist. 2000Ω Resistance 0...2000Ω
Resist. 5500Ω Resistance 0...5500Ω
Pt100 -200..850
o
C
Pt100-200...850ºC
Pt250 -200..600
o
C
Pt250-200...600ºC
Pt250 -200..850
o
C
Pt250-200...850ºC
Pt500 -200..180
o
C
Pt500-200...180ºC
Pt500 -200..850
o
C
Pt500-200...850ºC
Pt1000 -200..250
o
C
Pt1000-200...250ºC
Pt1000 -200..850
o
C
Pt1000-200...850ºC
Ni100 -60..180
o
C
Ni100-60...180ºC
Ni1000 -60..150
o
C
Ni1000-60...150ºC
Ni100-LG -60..180
o
C
Ni100-LG-60...180ºC
Ni1000-LG -60..180
o
C
Ni1000-LG-60...180ºC
Cu100 50..180
o
C
Cu100-50...180ºC