5.5.1.9. Displayed value range limitation
The value range limitation applies only to the main input,
so that it influence only thedisplayedvalue
DisplVal
.The value
range limitation parameters are located in the menu in the group
of
Display
parameters:
Over Lo
–lowerdisplayvaluethreshold
and Over Hi – upper display value threshold. The default value
of upper overflow is 99999 , and for lower overflow -99999.
If the lower display overflow occurs the
vvvvvv
, symbol is dis-
playedon thedisplayandthenumber valueofthedisplayedvalue is
setto-1e20.Iftheupperdisplayoverflowoccursthesymbol
isdisplayedonthedisplayandthenumbervalueofthedisplayedvalue
issetto+1e20.
5.5.2. Analog output
The P30U transducer is equipped with one current type
(source)orvoltagetypeanalogoutputdependingonthevariantcode.
5.5.2.1. Analog output individual characteristic
The P30U transducer enables processing displayed value,
second displayed value and the real time clock value into analog
output signal based on the individual linear characteristic
of the analog output. On the basis of coordinates of two points
provided by the user, the transducer determines (using a system
ofequations)aandbindividualcharacteristiccoefficients.
whereX1 inandX2 in–thedisplayedvalue,
Y1 out andY2 out–expectedvalueontheanalogoutput.