42
treated as the measured value (register 8000). If the request refers
toalargernumberofregisters(parameterNo.ofVal1),thenitis
possibletodisplay,atthebottomrowofthedisplay,thevalueofother
register than the first one being polled, because all the polled regi-
stersarecopied totheblockof registersfromtherange 8000...8049.
For example, when we want to display additionally the value
of the second register being polled, we should set the value “8001”
in the menu of the parameter Display→ Disp.Reg. (the first
valuebeingpolledisintheregister8000anditistreatedasthemain
displayedvalue)orenterthevalue“8001”intotheregister4024.
InordertomakethetransducerRS-485interfaceworkagain
in the Slave mode, one should select proper mode in menu RS-485
Mbus 485 → Mode → Slave.
Fig.9. Example of using a P30U transducer in the RS-485 Master
mode to read and register relative humidity from a P18 transducer.