User Manual CM-CAN1
3-5
3 Commissioning and configuration
DE
EN
1
2
3
4
5
6
7
A
3.5 Data handling
3.5.1 Saving settings
All configuration data can be backed-up with the KEYPAD on a SMART-
C
ARD or with the DRIVEMANAGER as a file. A parameter set in the
D
RIVEMANAGER always comprises three files with the extensions *.00D,
*.00T and *.00X. The D
RIVEMANAGER file selection boxes only ever
display the *.00D file.
3.5.2 Restoring
factory defaults
Note: In both cases it takes around 10 seconds for the device to
signal that it is ready again. During this time the device per-
forms a self-test and changes all its settings to the factory
setting. This setup is only retained when the data are backed-
up in the device, however. Data backup is initiated by way of
the D
RIVEMANAGER user interface or by writing to parameter
150-SAVE = (1)START by way of the bus system.
Attention: Data backup takes a few hundred milliseconds.
During that time the device must not be switched off, other-
wise the settings will be lost.
Parameter 150-SAVE is automatically set to (0)STOP by the device after
the save operation. This process can be used for timeout monitoring of
the function.
Function Effect
• Parameter 04-PROG = 1
(subject area _86SY System)
➢ All parameters of the current user
data sets up to user level MODE = 4
are reset to their factory defaults.
• Press and hold down both cursor
keys during power-on.
➢ All parameters in all user data sets
up to user level MODE = 5 are reset
to their factory defaults.
• Parameter 4-PROG = 850
(...)
➢ All parameters in all user data sets
up to user level MODE = 6 are reset
to their factory defaults.