User Manual CM-CAN1
4-11
4 Setting the device parameters
DE
EN
1
2
3
4
5
6
7
A
573-CACTR - Control word
The control word received via the control identifier is entered in parameter
573-CACTR. During commissioning the parameter can be used to check
the reception of data. The parameter is for display purposes only.
572-CASTA - Status word
The status of the preset state machine is entered in parameter 572
CASTA. The data content of the parameter corresponds to data bytes 0
and 1 in the status identifier. The parameter is for display purposes only.
288-FOPT2 - Reference from option slot 2
The reference value received via the control identifier is entered in param-
eter FOPTx. The data content of the parameter corresponds to data bytes
2-5 of the control identifier. The interpretation of the value is dependent
on the selected operation mode. The parameter is for display purposes
only.
4.3.3 Data backup
150-SAVE - Back-up device setup
Parameter to back-up the complete device setup to the Flash memory. All
parameters are first held in the RAM. So that the parameters are available
again after power-off, they must be backed-up. To do so, parameter
150-SAVE is set to 1 after all other parameters have been set. The save
operation takes a few hundred milliseconds. During that time the drive
Subject area Value range Factory set. Unit Data type Memory type
_57OP 0000H ... FFFFH 0000H –USIGN16
RAM actual
value
Subject area Value range Factory set. Unit Data type Memory type
_57OP 0000H ... FFFFH 0000H – USIGN16
RAM actual
value
Subject area Value range Factory set. Unit Data type Memory type
_28RS -32764 ... 32764 0 Hz INT32Q16
RAM actual
value