4-8
User Manual CM-CAN1
4 Setting the device parameters
489-CLBDR - CAN bus baud rate
By way of this parameter the baud rate of the CAN controller is set.
Attention: A change of device address or baud rate only takes effect
after the next reset (restart) of the inverter!
Before the reset save the settings in the device with parame-
ter 150-SAVE!
574-CAWDG - Bus watchdog time in ms
Value for watchdog to monitor the CAN bus. The watchdog time is adjust-
able in millisecond increments. The value 0 deactivates the watchdog.
Subject area Value range Factory set. Unit Data type Memory type
_57OP 25 ... 500 500 kBaud USIGN8 FLASH
CLBDR
*
Transmission speed Comments
0 500 kBaud Factory setting
1 250 kBaud
2 125 kBaud
3 75 kBaud
4 50 kBaud
5 25 kBaud
* - Transfer value for parameter setting
Table 4.7 Baud rate
Subject area Value range Factory set. Unit Data type Memory type
_57OP 0 ... 255 0 ms USIGN8 FLASH