User Manual CM-CAN1
4-19
4 Setting the device parameters
DE
EN
1
2
3
4
5
6
7
A
Plausibility checks:
After data block 1 the drive unit verifies the access rights to the parame-
ter. If the status is unequal to 0, communication is terminated for the
parameter.
If the master transmits more than 100 characters for a string, the string is
not saved and the error is entered at the end of the block sequence in the
status (bit 7 = 1).
If the checksum in the last telegram is not identical to its own, a telegram
repetition is requested by setting of bit 4 in the status.