EasyManua.ls Logo

Lutron Electronics Grafik Eye GRX-4000 Series - Step 6: Set Function Switches

Lutron Electronics Grafik Eye GRX-4000 Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
S
ELECT
V
ALUE
D
ISPLAYED
Load Type
Circuit
Control and Zone Assigned
Using circuit schedule
Value
3
4
5
1 Inc/Mag LV
2 Fluorescent
3 Neon/CC
S
ELECT
V
ALUE
V
IEW
V
ALUE
4 Non-dim
5 Elec. LV
Unassigned
S
ELECT
C
IRCUIT
Link Status
Using Zone Capture
Low End Trim (optional)
High End Trim (optional)
Circuit Level
TM
®
Power OK (Pins 1,2)
Data OK (Pins 3,4)
2
1
STEP 10: Address GRX-4000 Control
Units
Push the scene 1 button on a GRX-4000 Series
Control Unit. The scene 1 LED should go on.
Address Control Unit as follows:
A. Push and hold top and bottom scene buttons until
scene LEDs begin to cycle.
B. Push FADE button until ‘A-’ is displayed in the
FADE window. If A1 through A8 appears, then go
to D since the Control Unit is already addressed.
C. Push MASTER button once. The control will
automatically choose the next available address.
Note the address of each on the Control Directory
(A1-A8).
If a Control or Load Directory already exists, push
MASTER and buttons to have the address
match these directories.
D. Push and hold the top and bottom buttons until the
scene LEDs stop cycling.
Repeat Steps A-D on all GRX-4000 Series Control
Units.
SM
LUTRON
FADE OVERRIDE
ZONE
MASTER
ZONE 6ZONE 5ZONE 4ZONE 3ZONE 2ZONE 1
A,D
B
C
GRX-4000 Series Control Unit
For More Information...
Troubleshooting Guide.................24, 25
Control Directory...............................27
?
Address GRX-4000
Control Units
As soon as a GRX-4000 Series Control Unit is
addressed, check that the Data OK LED (located
below the Power OK LED on the Circuit Selector)
begins to blink. Blinking indicates that the wiring from
a GRX-4000 Series Control Unit to the panel is
correct.
Note:
As soon as a GRX-4000 Series Control Unit is
addressed, Accessory Controls will no longer have
any affect on the GRX-4000 Series Control Units.
The Accessory Controls will be reactivated in
Step 16.
Not lit before addressing
Blinking after
addressing
(approximately once per
second)
Step by Step instructions for GRAFIK Eye Switching Panel