18
Circuit Selector in
Normal (Non-Essential)
Panel
Circuit Selector in
Emergency (Essential)
Lighting Panel
SW6 SW6
Move left Move right
SELECT VALUE DISPLAYED
Load Type
Circuit
Control and Zone Assigned
Using circuit schedule
Value
3
4
5
1 Inc/Mag LV
2 Fluorescent
3 Neon/CC
SELECT VALUE
VIEW VALUE
4 Non-dim
5 Elec. LV
Unassigned
SELECT CIRCUIT
Link Status
Using Zone Capture
Low End Trim (optional)
High End Trim (optional)
Circuit Level
TM
®
Power OK (Pins 1,2)
Data OK (Pins 3,4)
2
1
Set Normal/Emergency
Switch
SELECT VALUE DISPLAYED
Load Type
Circuit
Control and Zone Assigned
Using circuit schedule
Value
3
4
5
1 Inc/Mag LV
2 Fluorescent
3 Neon/CC
SELECT VALUE
VIEW VALUE
4 Non-dim
5 Elec. LV
Unassigned
SELECT CIRCUIT
Link Status
Using Zone Capture
Low End Trim (optional)
High End Trim (optional)
Circuit Level
TM
®
Power OK (Pins 1,2)
Data OK (Pins 3,4)
2
1
STEP 16: Set Normal/Emergency Switch
(Non-Essential/Essential)
Note:
This step is only performed if there are any panels
with Emergency (Essential) Lighting Circuits on
the job.
Panels are shipped with Switch 6 (located at the base
of each Circuit Selector) in the center position for
operation without any Emergency (Essential) Lighting
Circuits.
Identify a panel supplied with Normal (Non-Essential)
power. Move its Switch 6 to the left position.
For all the Emergency (Essential) Lighting Panels,
move switch 6 to the right position.
In this arrangement, the Emergency (Essential)
Lighting Panel will “sense” the Normal (Non-Essential)
Panel’s power. When Normal (Non-Essential) power
is removed, the Emergency (Essential) Lighting will
go to ‘ord’ override levels (factory set to ON).
Loss of Normal (Non-Essential) power can be
simulated by turning off all connected Normal (Non-
Essential) Panels’ Control Breakers.
When Switch 6 is left in its center position (as
shipped), terminal 5 has no affect on the Circuit
Selector operation.
Notes:
If there is no Normal Panel, contact Lutron
for GRAFIK Eye 4000 Application Note #5:
How to
create a ‘sense’ line.
Override (‘ord’) Level is factory set to turn all circuits
ON. If the override level is to be OFF, contact Lutron
for GP Panel Advanced Function #1.