12
Remove Bypass
Jumpers
STEP 11: Remove Bypass Jumpers
Repeat Step 7 if load wiring has been modified.
Turn circuit breakers OFF.
Danger - Do not remove or replace
bypass jumpers while power is ON.
Loosen both screws of each bypass jumper.
Remove and store the bypass jumpers for possible
later use.
Store the bypass jumpers at the bottom of the panel.
DO NOT place them on top of the module.
Warning - When working on any load
(such as replacing a bulb), turn Off
power to the module that powers the
load. Turn the module power off by
switching its input circuit breaker
(MCB) Off.
Turning ON to a load fault WILL
irreparably damage the switch module.
Damage caused by short circuits and
miswiring is not covered in the product
warranty.
Turn Circuit Breakers ON.
BYPASS JUMPERS—
Replace whenever a load
is serviced.