28
Maintenance
XP Series Panels
Danger - Any liquid entering the panel
may reach internal components, cause
personal injury, damage the equipment,
and void the warranty.
1. If any extra wiring is brought into the panel,
temporarily cover the modules and thoroughly
remove all metal chips, wire strands, insulation,
or other debris before reapplying power.
2. In the unlikely event of damage to switching
equipment, replace bypass jumpers (see step 11).
This will take the switching equipment out of the
circuit and apply full power to fixtures.
3. To take manual control of the On or Off state of any
circuit, use the Circuit Selector (see Troubleshooting
Guide).
4. The exterior of the XP Panel may be painted as
follows:
a. Remove the front cover.
b. Cut a piece of paper slightly smaller than the
cover label (label is 7" x 2.675" with rounded
corners)
c. Tape the cut paper onto the label so that the tape
holds the paper and completely covers the
label. Avoid taping any of the label except the
outside edge.
d. For the cover or painted enclosure, sand the
existing paint to roughen it. For galvanized
enclosure - wipe the outside (do not paint the
inside) surface with a damp, soapy cloth.
e. Paint the cover or enclosure exterior. For
galvanized enclosure, use an acrylic (OVM
recommended) or urethane paint - not an oil
based paint.
Warning - When painting the panel cover,
keep all vent holes open and clear of any
paint pooling.
Danger - Turn power off before working on
any load. Each circuit may have an
individual, external disconnect switch.
Locate and lock the appropriate
disconnect switch (usually a breaker)
before servicing.
Warning - When working on any load
(such as rewiring a load), replace the
bypass jumpers to protect the switching
module until the load is proven.
Maintenance
Reference Sheet
Reference Sheets for GRAFIK Eye Switching Panel
GRX-4000 Series Control Units and Accessory
Controls
Clean front surface of control with a soft towel
moistened with a mild soap solution (non-
ammonia- based). Clean approximately every six
months.
Caution - Do not spray cleaning solution
onto control as it may reach internal
components.
Fixtures
It is important that lamps are maintained properly to
prevent what may appear as switching equipment
malfunctions. When lamps begin to fail on a circuit,
Lutron recommends group relamping of the entire
circuit.