Switched Hot
Load 16 A max
Neutral
Hot/Live In
Ground
H
SH
H
SH
H
SH
H
SH
H
SH
H
SH
H
SH
H
SH
Neutral
Dedicated Hot/Live
N
N
H
H
Wire System
STEP 3: Wire System (cont.)
Suggested wiring when panels are close together
Suggested wiring when panels are far apart
Notes:
• Terminal blocks accept one #14 AWG (2.5mm
2
)
through #10 AWG (4.0mm
2
) or two AWG #18 AWG
through #16 AWG wire.
• Two modules and the control feed are shown to the
left. The module terminal blocks are typical of the
rest of the possible 12 modules
• Lutron recommends that the Control Feed be a
dedicated circuit even though the control wiring
will draw 0.5 Amps max.
Danger - An XP Series panel is fed by
multiple circuits. Locate and lock each
feed in the OFF position.
Caution - XP Series panels require entry
of wires as specified. Improper entry will
block serviceable parts or violate NEC codes.
Warning - Do not remove bypass jumpers
at this step.
Caution - Lutron recommends the use of
a trough for ease of wiring (where space
permits).
Caution - Follow all local wiring codes.
5
Module wiring
Splice Neutrals
in Trough
Switched Hot/Live
Wire (SH)
SH
H
XP Panel
H
H
Load 16A Max.
N
SH
SH
N
Neutral
Wire (N)
Small
Distance
Hot/Live
Wire (H)
Distribution Panel
Load 16A Max.
N
SH
Neutral Wire (N)
Large
Distance
H
N
H
Switched Hot/Live
Wire (SH)
XP Panel
Reference Sheets for GRAFIK Eye Switching Panel
Hot/Live
Wire (H)
Distribution Panel