57-645 Eclipse Guided Wave Radar Transmitter - PROFIBUS PA
™
Reference Conditions Reflection from liquid of selected dielectric at +70° F (+20° C) with 72" probe
Linearity <0.5 inch
Measured Error Upper layer ±1 inch
Interface layer ±1 inch (clean distinct interface required)
Upper Layer Dielectric 1.4–5.0
Interface Layer Dielectric >15
Resolution ±0.1 inch
Repeatability <0.5 inch
Hysteresis <0.5 inch
Response Time <1 second
Warm-up Time <5 seconds
Operating Temp. Range -40° to +175° F (-40° to +80° C)
LCD Temp. Range -5° to +160° F (-20° to +70° C)
Ambient Temp. Effect Approximately ±0.02% of probe length/ ° C
Humidity 0-99%, non-condensing
Electromagnetic Compatibility Meets CE requirements (EN-61000-6-2/2001, EN 61000-6-4/2001)