How to troubleshoot 'EOP High' error on Magnetrol Measuring Instruments?
- EEmily WoodSep 1, 2025
If the End of Probe signal is out of range, ensure the Probe Length is entered correctly.
How to troubleshoot 'EOP High' error on Magnetrol Measuring Instruments?
If the End of Probe signal is out of range, ensure the Probe Length is entered correctly.
What to do if LEVEL reading is correct but LOOP is stuck at 4 mA on Magnetrol Transmitter?
If the LEVEL reading on the Display is correct, but the LOOP is stuck on 4 mA, the basic configuration data might be questionable. Set the POLL ADR to 0 if you are not using HART multi-drop.
Why is the LEVEL value reading high when it should be zero on Magnetrol eclipse 705 Measuring Instruments?
If the LEVEL value is reading high when it should be zero, the transmitter might be loose or disconnected from the probe. Ensure the transmitter is securely connected to the probe.
Why is LEVEL reading high when it should be zero on Magnetrol Transmitter?
If the LEVEL value is reading high when it should be zero, the transmitter might be loose or disconnected from the probe. Ensure the transmitter is securely connected.
How to resolve WeakSgnl error on Magnetrol Transmitter?
If you are getting a WeakSgnl error, the signal amplitude is lower than desired. Set the transmitter to a lower dielectric range and increase the sensitivity.
What does the 'Flooded?' message mean on Magnetrol Transmitter?
The 'Flooded?' message indicates a loss of level signal, possibly due to flooding (twin rod probes only). Decrease the level in the vessel and set the transmitter to a lower dielectric range.
Why are LEVEL and % OUTPUT values at maximum on Magnetrol Measuring Instruments?
If the LEVEL and % OUTPUT values are all at the maximum level, there might be a configuration issue with the single rod probe. Increase the Blocking Distance or increase the Dielectric Range.
What causes high LEVEL and % OUTPUT readings on Magnetrol eclipse 705?
If the LEVEL and % OUTPUT values are reading high compared to the actual level, there might be an obstruction in the tank affecting the single rod probe. Increase the Dielectric Range until the obstruction is ignored or relocate the probe away from the obstruction.
How to troubleshoot inaccurate LEVEL and % OUTPUT values on Magnetrol Measuring Instruments?
If the LEVEL and % OUTPUT values are inaccurate, the basic configuration data might be questionable, or the interface level may have significant emulsion. You can reconfigure the Probe Model, Probe Mount, Probe Length, or Level Offset. Also, examine the process to reduce or eliminate the emulsion layer.
What to do if the LEVEL reading is stuck at full scale on Magnetrol eclipse 705?
If the LEVEL reading on the display is stuck at full scale, the software might believe the probe is flooded. Check the actual level. If the probe isn't flooded, inspect for buildup or obstructions near the top of the probe. You may also select a higher dielectric range, check for condensation in the probe connection, or add Blocking Distance.