BE57-646 ECLIPSE Guided Wave Radar Transmitter - FOUNDATION fieldbus
CYCLE_TYPE: Identifies the block execution methods that
are available.
CYCLE_SEL: Allows the user to select the block execution
method.
MIN_CYCLE_T: The time duration of the shortest cycle
interval. It puts a lower limit on the scheduling of the
resource.
NV_CYCLE_T: The minimum time interval between
copies of non-volatile (NV) parameters to NV memory. NV
memory is only updated if there has been a significant
change in the dynamic value and the last value saved will be
available for the restart procedure.
NOTE: After completing a download, allow several seconds before
removing power from the ECLIPSE Model 706 FF transmitter to
ensure that all data has been saved.
FREE_SPACE: Shows the amount of available memory for
further configuration. The value is zero percent in a precon-
figured device.
FREE_TIME: The amount of the block processing time
that is free to process additional blocks.
SHED_RCAS: The time duration at which to give up com-
puter writes to function block RCas locations.
SHED_ROUT: The time duration at which to give up
computer writes to function block ROut locations.
FAULT_STATE, SET_FSTATE, CLR_FSTATE: These
only apply to output function blocks. (The Model 706FF
has no output function blocks).
MAX_NOTIFY: The maximum number of alert reports
that the transmitter can send without getting a confirma-
tion.
LIM_NOTIFY: the maximum numbers of unconfirmed
alert notify messages allowed. No alerts are reported if set to
zero.
CONFIRM_TIME: the time that the transmitter will wait
for confirmation of receipt of a report before trying again.
Retry will not occur if CONFIRM_TIME = 0.
WRITE_LOCK: When set to LOCKED, will prevent any
external change to the static or non-volatile data base in the
Function Block Application of the transmitter. Block con-
nections and calculation results will proceed normally, but
the configuration will be locked.
UPDATE_EVT (Update Event): Is an alert generated by a
write to the static data in the block.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Magnetrol Eclipse 706 and is the answer not in the manual?

Magnetrol Eclipse 706 Specifications

General IconGeneral
BrandMagnetrol
ModelEclipse 706
CategoryTransmitter
LanguageEnglish

Related product manuals