FD_OFFSPEC_MAP: Maps conditions to be detected as
active for the OFFSPEC alarm category.
FD_MAINT_MAP: Maps conditions to be detected as
active for the MAINT alarm category.
FD_CHECK_MAP: Maps conditions to be detected as
active for the CHECK alarm category.
FD_FAIL_MASK: Used to suppress an alarm from being
broadcast for single or multiple conditions that are active in
the FAIL alarm category.
FD_OFFSPEC_MASK: Used to suppress an alarm from
being broadcast for single or multiple conditions that are
active in the OFFSPEC alarm category.
FD_MAINT_MASK: Used to suppress an alarm from
being broadcast for single or multiple conditions that are
active in the MAINT alarm category.
FD_CHECK_MASK: Used to suppress an alarm from
being broadcast for single or multiple conditions that are
active in the CHECK alarm category.
FD_FAIL_ALM: Used to broadcast a change in the associ-
ated active conditions, which are not masked, for the FAIL
alarm category.
FD_OFFSPEC_ALM: Used to broadcast a change in the
associated active conditions, which are not masked, for the
OFFSPEC alarm category.
FD_MAINT_ALM: Used to broadcast a change in the
associated active conditions, which are not masked, for the
MAINT alarm category.
FD_CHECK_ALM: Used to broadcast a change in the
associated active conditions, which are not masked, for the
CHECK alarm category.
FD_FAIL_PRI: Specifies the priority of the FAIL alarm
category.
FD_OFFSPEC_PRI: Specifies the priority of the OFF-
SPEC alarm category.
FD_MAINT_PRI: Specifies the priority of the MAINT
alarm category.
FD_CHECK_PRI: Specifies the priority of the CHECK
alarm category.
FD_SIMULATE: Diagnostic conditions can be manually
supplied when simulation is enabled.
FD_RECOMMEN_ACT: Describes what actions can be
taken to address an active diagnostic condition.
BE57-646 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus