TOTAL_SP: The set point for a batch totalization.
OUT: The block output value and status.
OUT_RANGE: The high and low scale values, engineering
units code, and number of digits to the right of the decimal
point associated with OUT.
GRAND_DENY: Options for controlling access of host
computers and local control panels to operating, tuning,
and alarm parameters of the block (not used by the device).
STATUS_OPTS: Allows you to select option for status
handling and processing. The supported status option for
the Integrator block is: “Uncertain if Manual mode.”
IN_1: The block input value and status.
IN_2: The block input value and status.
OUT_TRIP: The first discrete output.
OUT_PTRIP: The second discrete output.
TIME_UNIT1: Converts the rate time, units in seconds.
TIME_UNIT2: Converts the rate time, units in seconds.
UNIT_CONV: Factor to convert the engineering units of
IN_2 into the engineering units of IN_1.
PULSE_VAL1: Determines the mass, volume or energy per
pulse.
PULSE_VAL2: Determines the mass, volume or energy per
pulse.
REV_FLOW1 : Indicates reverse flow when true”; 0-
Forward, 1- Reverse
REV_FLOW2: Indicates reverse flow when true”; 0-
Forward, 1- Reverse
RESET_IN: Resets the totalizers
STOTAL: Indicates the snapshot of OUT just before a
reset.
RTOTAL: Indicates the totalization of “bad” or “bad” and
uncertaininputs, according to INTEG_OPTIONS.
SRTOTAL: The snapshot of RTOTAL just before a reset
SSP: The snapshot of TOTAL_SP
INTEG_TYPE: Defines the type of counting (up or
down) and the type of resetting (demand or periodic)