Neg Ampl
xxx
S
uperuser
Superuser parameter Diagnostic parameter
Pos Ampl
xxx
Superuser
Superuser parameter Diagnostic parameter
Signal
xxx
None
Diagnostic Display
Indication of level
signal amplitude
Compsate
Superuser
Superuser Parameter
Select from None,
Manual, Auto
DrateFct
xxxx
None
Diagnostic Display
Compsate = Auto, velocity
derating factor
TargAmpl
xxxx
None
Diagnostic Display
Compsate = Auto, target
negative threshold amplitude
Targ Tks
xxxx
None
Diagnostic Display
Compsate = Auto, measured time of flight
from fiducial to target
Targ Cal
xxxx
Superuser
Diagnostic Display
Compsate = Auto, calibrated time of flight
from fiducial to target in room temperature
air
OperMode
(select)
Superuser
Superuser parameter
Compsate = Auto, select from Run, Cal,
Off
7xK Corr
xxx
Superuser
Superuser parameter
Probe Model = 7xK, Distance in mm from
fiducial to user
reference point
Snsr Val
xxx.x su
None
Distance to the target relative to the sensor
reference point.
CalPtLo
xxx.x su
Superuser
The lower calibrated point of Sensor Value.
It refers to PrLvl Lo.
In Sensor Units (Do Not Adjust)
CalPtHi
xxx.x su
Superuser
The higher calibrated point of Sensor
Value. It refers to PrLvl Hi.
In Sensor Units (Do Not Adjust)
ProbeLvl
xxx.x plu
None
Level on the probe relative to the end of
the probe.
PrLvl Lo
xxx.x plu
Superuser
Value of PrLvl at SnrCalLo. In Probe Level Units
PrLvl Hi
xxx.x plu
Superuser
Value of PrLvl at SnrCalHi. In Probe Level Units
ElecTemp
xxx C
None
Diagnostic Display
Present temperature in electronics
compartment (degrees Celsius)
Max Temp
xxx C
Superuser
Diagnostic Display
Maximum electronics
temperature recorded
Min Temp
xxx C
Superuser
Diagnostic Display
Minimum electronics
temperature recorded
SZ Hyst
xx.x su
Superuser
Superuser Parameter Safety Zone hysteresis height
37
57-640 Eclipse Guided Wave Radar Transmitter - FOUNDATION fieldbus
™