Part Number Preliminary 6/11 245
Diagnostics
SYMPTOMS
Premature harvest
Display indicates ITP Failure
Low ice production
Thin ice in bin
Freeze cycles are faster than published cycle
times
Will not harvest
Display indicates ITP Failure
Low ice production
Thick ice in bin
Large sheet of ice on evaporator
Harvest cycle doesn’t start
Freeze cycles are slower than published cycle
times
ICE MACHINE CYCLES INTO HARVEST BEFORE
ICE CONTACTS THE ICE THICKNESS PROBE
1. Reboot the control board by disconnecting and
reconnecting line voltage to the ice machine.
2. Verify ice thickness probe gap is approximately
9/32” (7 mm).
3. Wait six minutes:
Ice Machine remains in freeze cycle - Allow ice
machine to run.
Ice machine cycles into harvest - Replace ice
thickness probe to determine if problem is
resolved. If problem persists replace the control
board.