Part Number Preliminary 6/11 247
HIGH PRESSURE CUTOUT (HPCO) CONTROL
FUNCTION
Stops the ice machine if subjected to excessive high-
side pressure. The HPCO control is normally closed,
and opens on a rise in discharge pressure.
SPECIFICATIONS.
SYMPTOM
Opening the HPCO will cause the control board to
initiate a 10 minute delay. The display counts down
from 10 minutes to 0 minutes, at which point the ice
machine attempts a restart. If the HPCO is closed the
ice machine will continue to run. If the HPCO remains
open after the 10 minute delay or reopens when the
compressor starts, the ice machine will start another
10 minute delay period. The ice machine will lockout
after 10 failed attempts.
1. Machine is off and the display indicates
“Delay XX min, HPCO Active”
2. Machine is running and the display indicates
“HPC Fault” and an alert triangle
Specifications
Cut-Out Cut-In
440 psig ±10
(3103 kPa ±69 31 bar ±.69)
Automatic Reset
(Must be below 300 psig (2068 kPa 20.68 bar) to reset.)

Table of Contents

Other manuals for Manitowoc Indigo Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc Indigo Series and is the answer not in the manual?

Manitowoc Indigo Series Specifications

General IconGeneral
BrandManitowoc
ModelIndigo Series
CategoryIce Maker
LanguageEnglish

Related product manuals