Discharge Pressure High Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
page 151
Condenser Restriction
High inlet air temperature
Condenser discharge air recirculation
Dirty condenser fins
Defective fan cycling control
Defective fan motor
Improper Refrigerant Charge
Overcharged
Non-condensable in system
Wrong type of refrigerant
Other
Non-Manitowoc components in system
High side refrigerant lines/component restricted
(before mid-condenser)
Defective head pressure control valve
Water Inlet Valve is incorrectly adjusted (CVD1486
only)
NOTE: Do not limit your diagnosis to only the items
listed in the checklists.