68 Part Number: 040006847 12/19
Function
The bin thermistor stops the ice machine when the
bin is full. When ice cubes contact the bin thermistor
bulb holder, the bin thermistor opens and stops the
ice machine. When ice cubes no longer contact the bin
thermistor bulb holder, the bin thermistor closes and the
ice machine starts.
The bin thermistor “temperature setting” is determined by
the point of T2 (liquid line thermistor) at the time when T1
(sump water thermistor) comes below 2 °C. Refer to the
Specifications Charts below for clearance.
Specifications
UG18/UG20/UG30
Shut down
Power on
≤2.0 T2≤32 ≤1.7 ≥2.2
≤2.0 32 <T2≤51 ≤2.2 ≥3.7
≤2.0 51 <T2 ≤3.0 ≥4.5
UG40/UG50/UG65
Shut down
Power on
≤2.0 T2≤28 ≤1.5 ≥2.0
≤2.0 28 <T2≤56 ≤2.0 ≥3.5
≤2.0 56 <T2 ≤3.0 ≥4.5
UG80
Shut down
Power on
≤2.0 T2≤37 ≤1.5 ≥2.0
≤2.0 37 <T2≤56 ≤2.0 ≥3.5
≤2.0 56 <T2 ≤3.0 ≥4.5