3.6 FUEL CIRCUIT
The generator is diesel-powered by means of the
unions marked "DIESEL FUEL INLET" (rif.1) e
"DIESEL FUEL OUTLET" (rif.2); the latter serves to
return excess fuel.
The fuel pipes must be in hydrocarbon-resistant
rubber with an inside diameter of 8mm (0.31in).
For differences in level of more than 500mm (19.6in),
fit a single-acting check valve in order to prevent the
fuel system from emptying out.
Use a valve with 50mbar opening.
3.6.1 FUEL FILTER
The generating group is provided of fuel filter installed
inside the genset.
3.6.2 ELECTRIC PUMP
The electric pumpis equippedwith a protective filter
(ref.3).
The electric pump is cooled and lubricated with
the fuel. Do not activate the pump without fuel
in order to not damage it.
The feeding system has been developed for blow
out, in autonomous way, the air beads penetrated
inside the system.Activate the fuel pump for few
minutes before starting the generator to have
automatic bleeding.
To activate the fuel pump press the "START"
button (ref.5) for a moment.