6.19 ANOMALIES,CAUSES AND REMEDIES
The starter motor turns but the main engine does not start
- Check that there is fuel in the tank. (Fill up)
- Check if the stop electromagnet is in the firing position. (Consult Service Centre)
- Check that the emergency button is in ON position. (Turn it on ON position)
- Check that the DC thermal breakers are on. (Restore)
- Bleed the air bubbles from the fuel circuit.
The engine protection module is not activated when the START button is pressed
- Check that the termal protection switch is open. (Restore the contact pushing the button)
- Check battery cables and clamps, and electrical connections. (Reconnect)
- Check integrity of the battery. (Recharge or replace)
The generator switches off during the operating period
- Checkifa protectionhasbeenactivatedwiththerelevantlightcomingon.(Removethecauseandretry starting)
- Check if there is fuel in the tank. (Fill up)
There is a high grade of smoke at the engine exhaust
- Check that the oil level in the sump does not exceed the MAX index. (Restore level)
- Check that the generator is not in overload.
- Check calibration of the injectors. (Consult Service Centre)
The engineruns irregularly
- Check the fuel filters. (Replace)
- Bleed the air bubbles from the fuel circuit.
The alternator voltage is too low
- Check the engine rpm: 1575-1590 rpm (52.5 - 53Hz) without utilities connected.
- Check that there is not a too heavy load. (Reduce the load)
- Capacitor breakdown. (Contact Service Centre)
- Alternator failure. (Contact Service Centre)
- Check all electricalconnections. (Contact Service Centre)
Starter battery flat
- Check the electrolyte level in the battery. (Restore the level)
- Check functioning of the DC alternator.
- Check integrity of the battery.
The generator does not deliver power
- Check that the magnetothermal switch is in the “ON position. (Contact Service Centre)
- Capacitor breakdown. (Contact Service Centre)
- Alternator failure. (Contact Service Centre)
- Check all electricalconnections. (Contact Service Centre)
6.20 HOW TO ORDER THE SPARE PARTS
In order to ensure a good functioning of the generator, we recommed to use original spare parts only.
The spares can be purchased from the customer authorized assistence network (consult the SERVICE manual
enclosed with the generator).
You can get anyfuther information contacting customer centralService.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mase Generators IS 6.1 and is the answer not in the manual?

Mase Generators IS 6.1 Specifications

General IconGeneral
BrandMase Generators
ModelIS 6.1
CategoryPortable Generator
LanguageEnglish

Related product manuals