EasyManua.ls Logo

MAXA HI-T - Help Page

MAXA HI-T
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HiTCentralizedcontroller
22
41/44 Bitmapforcingicons Numb 0 0 4095
42/44 Dewpointtemp.margin °C 5.0 0.0 50.0
43/44 Min.stayingtimeindehumidification Seconds 300 0 600
44/44 Max.stayingtimeindehumidification Seconds 600 0 1200
Table4.Keyboardmenuserviceparameters.
Thefancoilserviceparametersareshowninthefollowingtable:
N. PARAMETERSNAME UNIT DEFAULTVALUE MINIMUMVALUE MAXIMUMVALUE
1/9 Knoboffset °C 0.0 0.0 15.0
2/9 Hotstartsetpoint °C 0.0 0.0 50.0
3/9 Toocoolsetpoint °C 0.0 0.0 50.0
4/9 TOFFfanforHeatfloor Minutes 0 0 255
5/9 TOFFfanforHeatceiling Minutes 0 0 255
6/9 TOFFfanforCool Minutes 0 0 255
7/9 TONfanforHeatfloor Seconds 0 0 255
8/9 TONfanforHeatceiling Seconds 0 0 255
9/9 TONfanforCool Seconds 0 0 255
Table5.Fancoilservice’sparameters.
Tochangeathevalueofaparameter:
enteredintheparameterlistofchillers,fancoilsorkeyboard,usetheupanddownarrowstoscrollthroughpagesofthe
parameters,untilyoufindthedesiredparameter;
Pressonthecurrentlysetvalue;
thepresentvalue
turnsredtoindicatethatitcanbechangedbyusingtheupanddownarrows;
Selectthedesiredvalueandpresstheconfirmationtick.
Note:Ifyoupressoutsidetheconfirmationarea,itreturnsagainthepreviouslyvalue.
3.6.5.3 MANUFACTURERMENU
Toaccesstothemanufacturermenu
youmustsetthemanufacturerpassword.
Fromhereyoucan:
accesstothemanufacturerparametersofthechiller,bypushingon"Chiller";
accesstothemanufacturerparametersoftheHiT,bypushingon"Keyboard".
3.6.6 HELPPAGE
Ontheinstructionsaregivenguidanceonthemeaningoftheicons;inthelistthatappears,foreachiconisindicateditsfunction.

Table of Contents