EasyManua.ls Logo

MAXA HI-T - Measurement of Temperature and Humidity; Dew Point and Dehumidufucation Control

MAXA HI-T
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HiTCentralizedcontroller
34
Note:Ifinthechillerisconfiguredthepresenceofadigitalinputtothemanagementofthesecondsetpoint(chillerparameterH44
=26,terminalsSESE,ref.Chillermanual),themanagementofthehumiditycontrolisnotdonefromtheremotecontrol.
Thedigitalinputisalso
possiblyusedforswitchbetweenthefirstandsecondsetpointduringoperationinwintermode.
Withdoublesetpoint functionenabled,ifthechillerworksonthesecondsetpoint(radiantpanelsside),thedoublesetpointicon
appearsinthetoolbarofthefunctionsinthepagesof
chillersandfancoilsanditremainstransparent.
If,however,thechillerswitchtothermoregulateonthefirstsetpoint(fancoilside),thedoublesetpointiconappearscolourful.
Similarly,the entryintodehumidificationis markedinthe functionbarofchillers andfan coilsbythe transitionfromtransparent
icontocolourfulicon.
WithparametersH82>1:
FLOORSIDEFUNCTION
(2°SETPOINT)
FANCOILSIDEFUNCTION
(1°SETPOINT)
DOUBLESETPOINTICON
ICONDEHUMIDIFICATION
ifdehumidificationisactive
Table8.Doublesetpoint/dehumidificationicon.
Inaddition, inthe homepage,youwill see avisual indicationof activationofthefan coildehumidification
(seeFigure 9.Fan coil
dehumidification.).
4.9.1 MEASUREMENTOFTEMPERATUREANDHUMIDITY
TheambienttemperatureandtherelativehumiditymeasuredbythesensorsbuiltintotheHiTremotecontrol,areavailabletothe
chiller,whichcanthenusethesevaluesmeasuredfortheirregulators,whererequired.
4.9.2 DEWPOINTANDDEHUMIDUFUCATIONCONTROL
Giventheenvironmentaltemperatureandthehumidity,theHiTremotecontrolcalculatesthedewpoint.
In operation of the plant in summer mode, with the double setpoint function active on chillers and thermoregulation normally
madewiththeradiantpanels(secondsetofwork),itactivatesacontroltokeep
thedewpointofatleastaquantitydefinedbythe
keyboardmaintainerparameterPar42/44:"Dewpointtemp.marginCbelowtheambienttemperaturedetectedbythecontrol
itself.
Instead,whenambienttemperature<DewPoint+Margintemp.Point:
Thefancoilsfordehumidificationturn
on.
Thechillerstartworkingwiththesetpointforthefancoils.
Thepermanenceremainsinthisstatusuntilthetemperaturereturnsto:

Ambienttemperature≥Dewpoint+Dewtemp.margin+1°C.
Even in the case where the above condition is verified, it remains in the status of dehumidification for at least the time set by
maintainerparameterPar43/44:"Min.
stayingtimeindehumidification",inordertoavoidannoyingoscillations.
Iftheaboveconditionis notsatisfiedafteramaximumtime givenbythemaintainerparameterPar44/44:"MaxDehumidification
time",themachinecomesoutfromdehumidification.Toavoidreturningimmediately,inthiscaseitrequiresaminimum
stayingin
adjustmenttotheradiantpanels,stillgivenbyPar43/44:"Max.stayingtimeindehumidification".

Table of Contents