4.10 CLIMATIC COMPENSATION
Itispossibletocompensatethesetpointaccordingtooutdoortemperature,inadifferentwaybetweenheatingandcoolingmodes,
firstandsecondsetpoint.
Insuchacasebesurethattheb08parameter(Systemmainpage‐>Configuration‐>Servicemenu‐>Parameters‐>Chiller‐>Chiller
name‐>b08:
Enab.dynamicsetpoint)isdisabled(=0)onthechiller.
Setpoint
T ext
Set
Set Text
Offset
Offset
m2
m1
Setpoint
T ext
Set
Set Text
Offset
Offset
m2
m1
Figure29.Climaticcompensation.
Set=Twater,TwaterECOoT
2
water,T
2
waterECO,settablefromthepage:Setpointsetup‐>“Chiller”.
Offset = offset settable from the page: Setpoint setup‐> “Chiller” (the variable Offset appears only if the “m”
coefficientshavebeenconfigured).
SetText, m1,m2= parameterswhichcan be
setfrom: Configuration”‐>Servicemenu‐> Parameters‐> Keyboard
(seeparameterslistinTable4).
Toexcludetheclimaticcompensationbytheuser,youhavetosettozeroalltheoffsetsinthemenuSetpointsetup‐>“Chiller”.
To exclude the climatic compensation
by the service,you have to setto zero the mcoefficientsin the service menu,keyboard
parameters.
Theoutdoortemperatureisdetectedbyadedicatedsensoralreadywiredtotheheatpump.
4.11 OTHER FUNCTIONS
ForanyinformationrelatedtootherfunctionsofthechillerorofthefancoilswhichareshownintheHiTdisplay(e.g.enablingor
activationofplantelectricalheater,sanitaryelectricalheater,boilerintegration,defrostingcycle,watersideorairsideantifreeze
heaters,etc…),pleasereferto
chillerorfancoilmanuals.
4.12 SPECIALFUNCTIONS
Fromthemainmenu,choosingtheicon“additionalfunctions”,yougotothefollowingmenu: