Hi‐TCentralizedcontroller
36
Figure30.Page"Specialfunctions".
Theavailablefunctionsaredescribedinthefollowingparagraphs.
4.12.1 SCREEDFUNCTION
Bypressingtheiconrelatedtothescreedfunctionyouaccesstoanewmenuinwhichyoucanchoosewhichunitsshouldbe
enabledtothisfunction:
Figure31.Chillermultiplechoice,screedfunction.
Onceyouchoosethechillerswhichparticipatetothisregulation,thesystemhasthefollowingbehaviour:
• Alltheheatpumpsenabledinthescreedfunctionareforcedtoheatmode.
• Alltheheatpumpsnotenabledinthescreedfunctionareforcedtooffmode.
• Theheat
pumpsset‐pointisgivenbytheparameter“Screedfunctionset”,whichcanbesetamongtheserviceparameters
(Configuration‐>Servicemenu‐>Keyboard‐>Par36/44:”
ScreedfunctionSet”).
• The function has a duration given by the service parameter: Configuration‐> Service menu‐> Keyboard‐> Par 37/44: ”
Durationscreedfunction”.Aftersuchperiodthesystemreturnstotheprevioussettings.
4.13 PASSWORDANDPROTECTIONS
Therearemoreprotectionandpasswordlevels.
Aninitialdistinctionincludesthefollowingthreeaccesslevels:
‐ User’slevel
‐ Servicelevel
‐ Manufacturer’slevel
Toeachofthesethreedifferentlevelsyoucanaccessfromthe“Configuration”screen,previouslyinsertingadedicatedpassword.
Theuser’spassword,defaultsetto
“0”,canbemodifiedbyaccessingtouser’sparameters(seeParagraph3.6.5.1).
Theservice’spasswordcanbemodifiedbyaccessingtoserviceparameters(seeParagraph3.6.5.2).