 HiTCentralizedcontroller
29
Ifenabledthedoublesetpoint(fromHomeSystem‐>Configuration‐>ServiceMenu‐>Parameters‐>Chiller‐>Chillername‐>H82:
Enablesecondsetpoint=2,3,or4),(seeParagraph4.9),thepossiblesettingsforthechillerare:
DOUBLESETPOINT
4.6.4 FANSETUP
TosetthefanspeedrefertowhatisstatedinParagraph3.4.2.
4.6.5 PROGRAMSSETUP(CHRON OTHERMOSTAT)
Theprogrammingofthechronothermostatisdoneseparatelyonthechillerandonthefancoilterminals:youmustprogramboth
the activation and the deactivation of the chiller, and both the activation and the deactivation of the areas which are associated
with the fan coils; the activation of a programmed
area is not a sufficient condition to activate the chiller/chillers connected in
paralleltothesystem.
Fromthemainpageofthesystem,goto"Programs";
Nowyoucanchoosebetween5programs:
SummerChiller”,tosettheweeklytimeprogrammingofchillersincoolingmode;
“WinterChiller”,tosettheweeklytimeprogrammingofchillersinwintermode;
“SummerZone”,tosettheweeklytimeprogrammingofthezonesinsummermode;
“WinterZone”,tosettheweeklytimeprogrammingofthezonesinwintermode.
In addition, if is enabled the sanitary mode (from System main page> Configuration‐> Service menu‐> Parameters‐>
Chiller‐>
Chillername‐>H10:sanitarypresence=1),youcanaccesstotwootherprograms:
Sanitarymodetosettheweeklytimeprogrammingmodeofthechillerinsanitarymode.
“Legionelladisinfections”tosettheweeklytimeprogrammingofthelegionelladisinfectioncycle.
4.6.5.1
WEEKLYCHILLERPROGRAMMING
Forthechillercanbedefinedonthesevendays,independentlyandwithminimumstepsof15minutes,thestatusofoperations:

Off
Normaloperation(useofnormalwatercontrolset)
Economicaloperation(useofthesetofeconomicregulationofwater)
Theweeklyprogramminginsummeroperationisdistinctfromthatoneinwintermode.
CHILLER
WINTER SUMMER
SANITARY
Changethevalueofthesetwiththeupanddownarrowswithinthemaximumandminimumlimitsindicatedandconfirm
Sanitaryset
Waterset Waterseteco Waterset2 Waterseteco2
Waterset Waterseteco Waterset2 Waterseteco2