Hi‐TCentralizedcontroller
24
point,allowingacascadeoperation.Inparticular,theparameterstobesetinanetworkofthechillertobeconfiguredinacascade
are:
• Par8/44:numberofchillersinthenetwork(forcascadeoperation);
• Par9/44:Rotationperiod(forcascadeoperation);
• Par10/44:(default2.0
°C):differentialchiller(forcascadeoperation).
Inthecaseofcascadeconfiguration(Par8/44≠0),thesetpointofeachchillerischangedbyamultiplevalueoftheparameterPar
10/44(°C)(differentialchiller),accordingtoastep‐decalibration.AftereachperiodequaltoPar9/44
minutes,theprioritiesforthe
interventionofthechillerschange,byrotatingthedecalibrationofthesetpointofthechillers,inordertobalancetheloadonthe
variousmachines.Ifachillerisinalarm,itisexcludedfromtheregulation.BydefaultPar8/44=0.
4.3 CHILLER/HEATPUMPSMANAGMENT
WiththeremotecontrolHi‐T,upto7MAXAchiller(i‐HWAKV2/V2+seriesandi‐HPseries)willrun.Themainfunctionsregulated
are:
• ON/OFFcontrolling;
• Changeofseason(summer,winter,summerwithsanitarymode,winterwithsanitarymode,sanitarymode);
• Set‐pointsetting;
•
Displaycurrentalarms;
• Alarmhistoryresidinginthekeyboardwiththedateandthetimeoftheevent;
• Accesstotheparametersofthechiller(passwordprotected);
• Displayofthemainstatusesofthechiller;
• Weeklyprogramminginsummer,winter,sanitarymodeandofthelegionella
disinfectioncycle.
4.3.1 ENABLINGTHEINDIVIDUALCHILLERFORTHEPRODUCTIONOFSANITARYWATER
Of all the chiller in the network enabled to produce sanitary water, you can choose using the appropriate sub‐menu in “Status
setup”,whichofthesemayparticipateinthesanitaryproduction(seeParagraph4.6.2).Onlythoseselectedwillbeenabledtothe
productionofsanitarywater,alltheothers
areusedexclusivelyfortheplant.
4.4 FANCOILMANAGE
WiththeremotecontrolHi‐T,upto80MAXAfancoilwithHNSBox,dividedintoupto9zones,willhandle.Thesettingsofthefan
coilcanbemadeforindividualzones(notforindividualunits).Themainregulationfunctionsare:
‐ ON/OFF(systemand/orzonewith
itsscheduler);
‐ Season(system);
‐ Fanspeed(ofthearea);
‐ Dehumidificationcontrol.
TotheFancoilsisalsosenttheset‐pointofthezone.Itistakenintoaccounttheadjustmentmadelocallyontheknobofthefan
coil.
4.5 PROCEDUREBEFORESETTINGTHEHi‐TREMOTECONTROL
NOTE:Tofacilitatetheinstallationphaseandtheinterfacingofthekeyboardwiththehydronicterminals,itisadvisabletosupply
theterminalunitsseparately;eachterminalunitmustbeinterceptedbyitsswitch.
4.5.1 ADRESSING
Duringthefirststartitisnecessarytosupplyeachhydronic terminalseparately.Thephaseofaddressingisdoneaccordingtothe
followingsteps:
1. Poweronthefirstfancoil;
2. Fromthemainpageofthesystem,goto“Configuration”;
3. Enterinside“ServiceMenu”
;