 HiTCentralizedcontroller
23
4 STATUSMACHINESANDFUNCTIONS
4.1 NEWTORKMANAGEMENT
ThenetworkwhichisheadedbytheremotecontrolHiTcanbecomposedofamaximumof7 chiller/heatpumpsandupto80fan
coils.Forwhatconcernstheconfigurationofthenetwork,therearethefollowingfunctions:
addressingprocedureoffancoil;
automaticscanningofthe
networktodiscoverdevices;
radiantpanel’smanagement(accordingtothesetpoint).
4.2 REMOTECONTROLCONNECTEDWITHMORECHILLERINTHENETWORK
Intheeachonboardcontrolpanel,setthechiller(parameterH79)asdescribedabove.
ThenconnectthechillerandtheremotecontrolHi‐Tasshowninthedrawing.
IntheremotecontrolHi‐T,bysettingtheparameterPar8/44( Configuration‐>ServiceMenu>Keyboard
)relatedtothenumberof
chillers in the network , you can configure the network: with Par 8/44 = 0 all the chiller in network feature a similar operation
(paralleloperation,accordingtoasinglesetpoint),whilewhitPar8/44≠0wehaveadecalibrationonthe
stepsofthechillerset