8.4 DIP SWITCHES SETTING
ModifytheDipSwitchesinsidetheDRALNETcontrolasper:
Installedunit;
Waterunitinstallationposition;
Operationlogic.
DipSwitchesfunctions:
DipSwitchno. ON OFF Description
x Floorunit
1
x Ceilingunit
x Ondemandventilation(1)
2
x Continuousventilation(2)
x Valvethermalregulation
3
x Fanthermalregulation
DipSwitchno. Description
OFF OFF 2pipeandnoresistanceunit
OFF ON 4pipeunit
ON OFF 2pipewithsettingresistancesunit
4‐5
ON ON 2pipewithintegrationresistancesunit
NOTES:
(1)ondemandinheating,continuousincooling.
(2)noHotStartandTooCool.

DipSwitchessetting
Dip4OFF
DIP5OFF
Dip4ON
DIP5ON
Dip4ON
Dip5OFF
Dip4OFF
Dip5ON
System 2pipe 2pipe 2pipe 4pipe
System
type
Electricalresistances NO Integration Setting NO
Heating OUT1 OUT1‐OUT2
Cooling OUT1 OUT1 OUT1 OUT1
Outlets
Electricalresistances NO OUT2 OUT2 NO
ToentertheDIPSwitches,followthisprocedure:
First,separatetheconnectors’baseplatefromthemaininterfacebymeansofasmallscrewdriverinsertthescrewdriver
intothespecialholes(ontothecontainer’sside)andslightlytwistuntilthetwopartsaredivided;
Byturningthe
backofthemaininterface,itispossibletoseetheDipSwitchesfittedontotheprintedcircuitboard.
8.5 WATERPROBE
Installtheprobedownstreamthevalveandinsulateitbymeansofaluminiumtape;
Asforthe4pipesystems,ithasalwaystobefittedontothehotwatercircuit,andneverontothecoldwaterone;
UseonlytheprobesuppliedasaccessoryNTCtemperature
probe,reinforcedinsulation,PVCcable,cablelength=1,5m.
Note:Settheno.3DipSwitchontheONposition–valvethermalregulation.