EasyManua.ls Logo

MAXA HI-T - Dip Switches Setting; Water Probe

MAXA HI-T
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hi‐TCentralizedcontroller
46
8.4 DIP SWITCHES SETTING
ModifytheDipSwitchesinsidetheDRA‐LNETcontrolasper:
• Installedunit;
• Waterunitinstallationposition;
• Operationlogic.
DipSwitchesfunctions:
DipSwitchno. ON OFF Description
x Floorunit
1
x Ceilingunit
x Ondemandventilation(1)
2
x Continuousventilation(2)
x Valvethermalregulation
3
x Fanthermalregulation
DipSwitchno. Description
OFF OFF 2‐pipeandnoresistanceunit
OFF ON 4‐pipeunit
ON OFF 2‐pipewithsettingresistancesunit
4‐5
ON ON 2‐pipewithintegrationresistancesunit
NOTES:
(1)ondemandinheating,continuousincooling.
(2)noHotStartandTooCool.

DipSwitchessetting
Dip4OFF
DIP5OFF
Dip4ON
DIP5ON
Dip4ON
Dip5OFF
Dip4OFF
Dip5ON
System 2‐pipe 2‐pipe 2‐pipe 4‐pipe
System
type
Electricalresistances NO Integration Setting NO
Heating OUT1 OUT1‐OUT2
Cooling OUT1 OUT1 OUT1 OUT1
Outlets
Electricalresistances NO OUT2 OUT2 NO
ToentertheDIPSwitches,followthisprocedure:
• First,separatetheconnectors’baseplatefromthemaininterfacebymeansofasmallscrewdriver–insertthescrewdriver
intothespecialholes(ontothecontainer’sside)andslightlytwistuntilthetwopartsaredivided;
• Byturningthe
backofthemaininterface,itispossibletoseetheDipSwitchesfittedontotheprintedcircuitboard.
8.5 WATERPROBE
• Installtheprobedownstreamthevalveandinsulateitbymeansofaluminiumtape;
• Asforthe4‐pipesystems,ithasalwaystobefittedontothehotwatercircuit,andneverontothecoldwaterone;
• Useonlytheprobesuppliedasaccessory–NTCtemperature
probe,reinforcedinsulation,PVCcable,cablelength=1,5m.
Note:Settheno.3DipSwitchontheONposition–valvethermalregulation.