Id
Entering with the installer password, the status of the digital inputs can be view in this menu:
0 = input disabled
1 = input enabled
--- = input not congured
Par
Entering with installer password, in this menu you can modify the the main parameters of the unit. The parameters are collected in groups, each
group is idened by a three-digit code, while the index of each parameter is preceded by a leer.
Par DESCRIPTION INDEX OF THE PARAMETER
CnF Conguraon H--
ALL Alarms A--
CP Compressor C--
rE Regulaon b--
PUP Pump P--
Fro Electrical resistances r--
dFr Defrosng d--
LbH Minimum Hz L--
rEC Desuperheater rE
oHr
Entering with the installer password this menu displays the operang hours of the compressor (oH1) and of the circulator (oHP1).
It is possible to reset the displayed count by pressing the ESC key for 3 seconds
HiSt
This menu appears, aer entering the installer password, only if there is data in the alarm log.
Fir
Entering with the installer password, in this menu you can read rmware version (uEr), revision (rEu) and sub-revision (SUb).
This menu appears, aer entering the installer password, only if a USB key containing the relevant update les is connected to the card. The
available funcons are described below.
CAUTION: The access to the electrical panel is only allowed to QUALIFIED PERSONNEL.
FIRMWARE UPDATE [UPdF]
In case of rmware update, the following steps are necessary:
1. Copy the upgrade les into the main directory of a USB pen;
2. Set the unit to OFF on the keypad and remove power by seng the main switch to OFF;
3. Insert the ash drive into the USB port on the control;
4. Power up the unit, seng the mains witch to the ON posion;
5. Access the rmware update menu and start the procedure through the following sequence: PRG -> PSS -> PRG -> (enter installer password)
-> PRG -> USB -> UPdF -> PRG
6. A countdown advances on the display, at the end of the procedure the word "boot" appears and the 4 LEDs light up in sequence;
7. Switch o the unit, posioning the main switch on the OFF status;
8. Remove the drive from the USB port;
9. Switch the unit on by turning the main switch to the ON posion.
PARAMETERS UPDATE [UPPA]
In case of parameters update, the following steps are necessary:
1. Copy the upgrades les into the main directory of a USB pen;
2. Set the unit to OFF on the keypad and remove power by seng the main switch to OFF;
3. Insert the ash drive into the USB port on the control;