13
Controllo per i-32V5 MIDI Air/water inverter chillers and heat pumps with axial fans
NOTE:
CONTINUOUS OPERATION
The factory conguraon of the unit is for connuous operaon (P03 = 0). In this mode, the circulator is only switched o with the unit in OFF,
in all other cases it is on. When the unit goes into stand-by, the circulator is switched o with a delay that can be set by parameter P02 in tenths
of a minute (default P02 = 20, i.e. 2 minutes).
OPERATION ON CALL BY TEMPERATURE CONTROLLER
Subsequently, the compressor is also switched on, aer a delay me of P01 seconds (default P01 = 30) since the pump was switched on. In the
switch-o phase, the pump is switched o with a delay me of P02 minutes (default P02 = 2) from the switch-o of the compressor.
OPERATION ON CALL FROM TEMPERATURE CONTROLLER
�me
�me
�me
OPERATING ON CALL BY TEMPERATURE CONTROLLER WITH PERIODIC ACTIVATION
With P03 = 1, you can also congure the circulator to run periodically according to the following parameters:
• P16 = Periodic acvaon me interval (in minutes)
• P17 = Pump acvaon me (in seconds)
In pracce, when the pump is turned o for sased thermoregulaon, the countdown dened by parameter P16 begins and at each interval of
me P16 the circulator is turned on for a me equal to P17 seconds.
The funcon is disabled with P17 = 0 (default). The periodic funcon is suspended in the case of anfreeze mode intervenon.
OPERATION WITH INTEGRATION RESISTOR ACTIVE
If parameter r33 > 0, the circulator can also be switched on when the system and/or sanitary heang element is acvated.
ANTIFREEZE HYDRAULIC PUMP OPERATION
In this mode, the circulator is always on. Anfreeze operaon is enabled if the control temperature falls below P04 (default P04 = 5.0°C), it is
disabled if the control temperature rises above P04 + P05 °C (default P05 = 2.0°C).
PROPORTIONAL REGULATION
In cooling or heang mode, the speed of circulator changes depending on the temperature dierence between the inlet water and outlet water
of the heat exchanger according to the diagram below, where:
• P06 = Set ΔT water inlet/outlet in heang mode (default P06 = 4,0°C)
• P07 = Maximum speed (100%)
• P08 = Minimum speed
• P09 = Set ΔT water inlet/outlet in cooling mode (default P09 = 2,0°C)
• P10 = Modulang pump Delta (default P10 = 3,0°C)