23
Controllo per i-32V5 MIDI Air/water inverter chillers and heat pumps with axial fans
TABLE 4. OPERATIO IN SUBSTITUTION
INTERVENTION ORDER STATUS OPERATION r10 r15 r12 r16 r23 r24
1) Sanitary integraon heater
2) Aer r12 minutes, boiler
HEAT+SAN SANITARIO 0/1 0/1/2 /
Set the
minutes
2/3 2/3
1) Boiler
2) Aer r12 minutes, system/ sanitary
integraon resistence
HEAT /
HEAT+SAN
HEAT/SANITARY 0/1 0/1/2
Set the
minutes
Set the
minutes
6 3
1) System/ sanitary integraon resis-
tence
2) Aer r12 minutes, boiler
HEAT /
HEAT+SAN
HEAT/SANITARY 0/1 0/1/2
Set the
minutes
Set the
minutes
3 3
1) Boiler
HEAT /
HEAT+SAN
HEAT 0/1 0/1/2
Set the
minutes
/ 1/3/4/6 0/2
1) System integraon resistence
HEAT /
HEAT+SAN
HEAT 0/1 0/1/2
Set the
minutes
/ 0/2/5 1/3
1) Boiler HEAT+SAN SANITARY 0/1 0/1/2 /
Set the
minutes
2/3/5/6 0/1
1) Sanitary integraon resistence HEAT+SAN SANITARY 0/1 0/1/2 /
Set the
minutes
0/1/4 2/3
1) Boiler
HEAT /
HEAT+SAN
HEAT / SANITARY 0/1 0/1/2
Set the
minutes
Set the
minutes
3/6 0
1) System/DHW integraon resistence
HEAT /
HEAT+SAN
HEAT / SANITARY 0/1 0/1/2
Set the
minutes
Set the
minutes
0 3
Table 5 shows the sengs to be congured to enable the integraons COOL + SAN mode.
In this case, the only integraon that can be acvated is the domesc hot water integraon resistor and the division into operang bands does
not apply. The DHW integraon resistor is acvated when the set-point is sased aer r16 minutes from the compressor start-up or when the
set-point is not sased with the machine in lockout or alarm.
INTEGRATION INTERVENTION ORDER STATUS OPERATION r10 r15 r12 r16 r23 r24
1) DHW integraon resistance COOL+SAN SANITARY 0/1 1 /
Set the
minutes
0/1/2/3/4/5/6 2/3
Table 6 shows the behaviour of the plant and DHW integraon heaters in all the operang modes of the unit.
TABLE 6. INTEGRATION HEATERS OPERATION
STATUS OPERATION PLANT INTEGRATION RESISTENCE DHW INTEGRATION RESISTENCE
HEAT+SAN HEAT Works as indicated in TABLES 1, 2, 3 and 4.
DHW thermoregulaon takes precedence over
the system thermoregulaon, so if the thermo-
regulaon requires it, the machine switches to
"DHW" operaon and the DHW integraon resis-
tor behaves as indicated in TABLES 1, 2, 3 and 4.
HEAT+SAN SANITARY
Only if all 3 of the following condions are met: system
heater output congured, r24 = 1/3,remote system
water temperature probe present and congured.
the system integraon resis-
tor is acvated in the following cases:
• aer r12 minutes from the begin-
ning of its previously acvated count
in "HEAT" mode (see previous line);
• if not already acvated its counng in the
previous "HEAT" operang mode, aer r12
minutes from the thermoregulaon request.
In HEAT mode, with remote probe not con-
gured, the plant integraon resistor is de-
acvated or its counng is interrupted.
With open remote on-o contact, the
plant integraon resistor is deacvated.
Works as indicated in TABLES 1,2,3 and 4.
COOL+SAN SANITARY Not acve Works as indicated in TABLE 5.
COOL+SAN COOL Not acve Not acve
AUXILIARY SYSTEMS OFFSET MANAGEMENT
Seng osets, it is possible to establish that the boiler and/or integraon resistors (depending on the selected resources and priories) have a
higher setpoint in heang or DHW mode than the heat pump:
• r29 = temperature oset for boiler and system resistors rst set point (Hea);
• r30 = Temperature oset for boiler and system resistors second set point (Hea2);
• r31 = temperature oset for boiler and domesc hot water heaters (San).