EasyManua.ls Logo

MAXA i-32V5C MIDI 0121 - Parameters, Tables, and Alarms; Operating Bands and Offset Management

MAXA i-32V5C MIDI 0121
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
Controllo per i-32V5 MIDI Air/water inverter chillers and heat pumps with axial fans

OPERATING BANDS
The possible conguraons of the integraon parameters are listed in tables 1,2,3 and 4 shown below, divided by operang brackets (In the
boxes relang to the parameters rXX are indicated the possible values of the parameters for a given order of intervenon of the integraons to
occur in a given operaon of the machine).
TABLE 1. NORMAL OPERATING IN HEAT PUMP MODE
INTEGRATIONS INTERVENTION ORDER STATUS OPERATION r10 r15 r12 r16 r23 r24
1) System integraon resistence
HEAT/
HEAT+SAN
HEAT 1 0/1/2 / / 0/2/5 1/3
1) Boiler
HEAT/
HEAT+SAN
HEAT 0/1/2 0/1/2 / / 1/3/4/6 0/2
1) Plant integraon resistence
2) Aer r12 minutes, boiler
HEAT /
HEAT+SAN
HEAT 1 0/1/2
Set the
minutes
/ 1/3 1/3
1) Boiler
2) Aer r12 minutes, system integraon
resistence
HEAT /
HEAT+SAN
HEAT 1 0/1/2
Set the
minutes
/ 4/6 1/3
1) DHW integraon resistence HEAT+SAN SANITARY 0/1 1 / / 0/1/4 2/3
1) Boiler
HEAT+SAN/
COOL+SAN
SANITARY 0/1 0/1/2 / / 2/3/5/6 0/1
1) DHW integraon resistence
2) Aer r16 minutes, boiler
HEAT+SAN SANITARY 0/1 1 /
Set the
minutes
2/3 2/3
1) Boiler
2) Aer r16 minutes, DHW integraon
resistence
HEAT+SAN SANITARY 0/1 1 /
Set the
minutes
5/6 2/3
1) System/DHW integraon resistence
HEAT /
HEAT+SAN
HEAT/SANITARY 1 1 / / 0 3
1) Boiler
HEAT /
HEAT+SAN
HEAT/SANITARY 0/1 0/1/2 / / 3/6 0
1) System/DHW integraon resisitence
2) Aer r12 minutes, boiler
HEAT /
HEAT+SAN
HEAT/SANITARY 1 1
Set the
minutes
Set the
minutes
3
3
1) Boiler
2) Aer r12 minutes, system/DHW inte-
graon resistence
HEAT /
HEAT+SAN
HEAT/SANITARY 1 1
Set the
minutes
Set the
minutes
6 3
TABLE 2. JOINT OPERATION, BRACKET 1
INTERVENTION ORDER STATUS OPERATION r10 r15 r12 r16 r23 r24
1) Heat pump
2) Aer r12 minutes, system integraon
resistence
HEAT /
HEAT+SAN
HEAT 1 0/1/2
Set the
minutes
/ 0/2/5 1/3
1) Heat pump
2) Aer r12 minutes, boiler
HEAT /
HEAT+SAN
HEAT 0/1 0/1/2
Set the
minutes
/ 1/3/4/6 0/2
1) Heat pump
2) Aer r12 minutes, system integraon
resistence
3) Aer further r12 minutes, boiler
HEAT /
HEAT+SAN
HEAT 1 0/1/2
Set the
minutes
/ 1/3 1/3
1) Heat pump
2) Aer r12 minutes, boiler
3) Aer further r12 minutes, system in-
tegraon resistence
HEAT /
HEAT+SAN
HEAT 1 0/1/2
Set the
minutes
/ 4/6 1/3
1) Heat pump
2) Aer r16 minutes, system integraon
resistence
HEAT+SAN SANITARY 0/1 1 /
Set the
minutes
0/1/4 2/3
1) Heat pump
2) Aer r16 minutes, boiler
HEAT+SAN/ SANITARY 0/1 0/1/2 /
Set the
minutes
2/3/5/6 2/3
1) Heat pump
2) Aer r16 minutes, system integraon
resistence
3) Aer further r16 minutes, boiler
HEAT+SAN SANITARY 0/1 1 /
Set the
minutes
2/3 2/3

Table of Contents

Other manuals for MAXA i-32V5C MIDI 0121

Related product manuals