27
Controllo per i-32V5 MIDI Air/water inverter chillers and heat pumps with axial fans
Parame-
ter
Unit Default Visibility
Notes
r22
Upper limit Joint funcon I
band
°C 7 -16÷50 I Respect r22 ≥ r28 ≥ r08
It is recommended
not to change this
value, as this could
aect the operaon
of the unit
r23 Type of boiler use / 6 0÷6 I See par. 18.6
r24
Type of use integraon re-
sistors
/ 3 0÷3 I See par.18
r28
Upper limit for joint opera-
on 2nd band
°C -7 -16÷50 I Respect r22 ≥ r28 ≥ r08
It is recommended
not to change this
value, as this could
aect the operaon
of the unit
r29
Temperature oset for boil-
er
and system resistors rst
set point (HEA)
°C 0 0÷100 I See par.18.6
r30
Oset temperatura per cal-
daia
e resistenze impianto sec-
ondo set point (HEA2)
°C 0 0÷100 I
r31
Temperature oset for boil-
er
and sanitary heang ele-
ments (SAN)
°C 0 0÷100 I
r32 Boiler equipment / 1 0÷3 I See par. 18.6
r33
Pump management with ac-
ve resistors
/ 3 0÷3 I
L02
User enablement for mini-
mum Hz
/ 0 0÷1 I
0=funcon disabled
1=funcon enabled
L03 Minimum acve Hz / 6 0÷6 I
See chapter "16. MINIMUM HZ
FUNCTIONS".
rE01 Enabling DS in chiller / 0 0÷1
0=funcon disabled
1=funcon enabled
23. ALARMS
Some of the alarms that may occur on the unit are described below. When the control is switched o, the alarms are reset and the counts of the
relevant operaons are also reset. If the alarms are sll present when the machine is switched on again, contact technical assistance. The above
informaon may be subject to updates, in case of doubt please contact the company.
The water-side ow switch is already installed inside the unit and must not be tampered with or bypassed in any way.The ow switch is bypassed
by the control for a period of 10 seconds from the start of the machine, aer the bypass me the status of the digital input is considered, if it is
acve the presence of ow is considered. If a lack of ow is diagnosed for a me of at least 5 seconds, the alarm is acve and the circulator is
acvated for 120 seconds.
Once the ow of water is restored, the alarm is automacally reset, but if the alarm occurs more than 3 mes per hour, the reset becomes
manual.
The alarm is not acve in the following condions:
• during domesc hot water producon;
• during the system venng funcon.
If the water delivery probe detects a value higher than for longer than 50 seconds the alarm is acve. It deacvates when the temperature
returns below .
If the outlet water probe has a value lower than A08 (default A08 = 3,0°C), the alarm is acve. The deacvaon occurs if the temperature re-
corded by the same probe is higher than (default 6,0°C). The alarm is bypassed for 120 seconds aer switching on in heang mode.
This alarm is manual reset.
The corresponding alarm is acvated if any connected and enabled probe is short-circuited or interrupted. The alarm is also acve if the upper
limit of the probes (150C) or the lower limit (-50°C) is exceeded. A probe congured as a DHW probe does not give rise to an alarm if DHW pro-
ducon is not enabled.