17
Controllo per i-32V5 MIDI Air/water inverter chillers and heat pumps with axial fans
DHW CALL FROM DIGITAL INPUT
If DHW operaon is enabled and parameter H51 = 28, is set, as an alternave to using the DHW temperature probe (H17 = 0), the DHW funcon
can be acvated by closing/opening digital input DI7. The unit goes into DHW mode when the contact closes and exits DHW producon when
the contact opens.
The polarity of digital input ID7 can be inverted by seng H75 = 64.
This funcon is recommended when using two or more heat pumps in cascade, hydronically connected to the same domesc hot water storage
tank. In this case, the acvaon of the domesc hot water funcon can be set on the rst machine via the DHW probe of the tank, while the
other machines are automacally enabled thanks to the consent given by the digital input.
SYSTEM WATER REMOTE PROBE
In some system soluons (e.g.: heat pump in parallel with the boiler on the same hydronic circuit and exclusion diverter valve) it may be neces-
sary to enable a temperature probe of the system so that the on-board control can process the management correctly. The system remote probe
is acvated by seng parameter H18 = 41.
The system remote probe thermoregulates the heat pump only during the compressor start-up phase, the switch-o is managed by the probe
on the heat pump delivery.
In heang mode, the call is acve if the following condions are veried:
• Flow probe temperature < ;
• Temperature of the system remote probe < (default b22 = 5,0°C).
In cooling mode the call is acve if the following condions occur
• Flow probe temperature > ;
• Temperature of the system remote probe > (default b22 = 5,0°C).
14. DEFROSTING CYCLE
The defrost cycle is a funcon acve only in heat pump mode and is used to prevent the formaon of ice on the surface of the nned coil. The
formaon of ice on the evaporator, which occurs more frequently at very low external ambient temperatures, not only considerably reduces the
thermodynamic eciency of the machine, but also leads to the risk of damage to the machine itself.
15.
This funcon introduces a second working set-point on the plant side, both in cooling and heang mode.
The user terminal board allows a consent to be connected to switch from the rst to the second set-point and congured at digital input DI9 with
parameter H53 = 26. The valve,on the other hand, is connected in the terminal board to digital output DO7 and is congured via parameter H85.
Parameter VALUE
H53 26 Call for second set-point
H85 25 3-way valve for radiant panels
H129
0 Funcon disabled
1 Funcon congured but not acve
2 Enabled only in cooling mode
3 Enabled only in heang mode
4 Enabled in cooling and heang mode
16. MINIMUM HZ FUNCTIONS
Conguring parameter L02=1 and L03≠0 reduces the nominal operang Hz of the compressor.