Controllo per i-32V5 MIDI Air/water inverter chillers and heat pumps with axial fans
14
PROPORTIONAL REGULATION
[°C]
In pracce, in cooling mode, if the temperature dierence between the inlet and outlet is greater than P09 + P10, the circulator runs at maximum
speed, but if the dierence is less than P09 - 0.2°C, it runs at minimum speed; in the remaining cases, the pump modulates the speed propor-
onally. In heang mode, the same consideraons apply, replacing parameter P06 with parameter P09.
In sanitary producon the circulator always runs at maximum speed.
SYSTEM VENTING
The control allows the use of a manual system venng funcon with the circulator at maximum speed.
To enable the funcon the operaons to follow are:
• Set unit to OFF
• Access with maintenance privilege PRG -> PSS -> PRG -> (enter installer password) -> PRG
• Press UP and DOWN simultaneously for 3 seconds.
It is possible to exit the system venng cycle manually by pressing the MODE/ESC buon,or by pressing UP and DOWN keys simultaneously for
3 seconds.
water inside the system.
9. COMPRESSOR ON/OFF LOGIC
The restart of compressors is in operaon of a set point refered to the inlet and outlet water temperature. It is based on calculaon of that
is the dierence between outlet and inlet water temperatures, detected while the compressor for thermoregulaon is turning o.
REGULATION IN COOLING MODE
• Tw,out,set = setpoint in cooling mode
• = Tw,out,set – Tw,in,set
• b05 = compressor delta cut-o set = 0,2°C (default)
• b25 = delta cut-on regolazione compressor set = 2°C
RPM
Tw,out (outlet water temp.)
Tw,out,set
HzMin